CEILINGS

Blix Data Ceiling

Blix Data Ceiling is a suspended ceiling for data centres and data halls, where equipment can be hung anywhere along the profiles, even after installation. Each span carries up to 200 kg of suspended equipment, and the entire ceiling is accessible from below. The surfaces emit neither gases nor particles.

Technical room with Blix Data Ceiling and raised access floor, Blix Datagulv AS

Slotted aluminium grid for suspended equipment

Blix Data Ceiling is a suspended load-bearing grid in extruded aluminium with lay-in ceiling panels in galvanised steel. The system is supplied by Lindner Group under the system name Crossdata 55A, and is developed for data centres and clean rooms.

The profiles have a slot on the room side that takes hammer-head bolts and T-nuts. The bolts can be inserted anywhere along the profile and moved freely, even after the ceiling is installed. This means lighting and other equipment can be hung where it is needed, and moved when the installations in the data hall change. Unused sections of the slot can be closed with aluminium cover profiles.

The visible grid is 55 mm wide, and the standard module is 1200 x 1200 mm.

3D illustration of Blix Data Ceiling with metal ceiling panels in a grid and suspension rods, Blix Datagulv AS
Suspension field with metal ceiling panels in Blix Data Ceiling.

Load capacity

The grid carries up to 200 kg at the centre of a span and 325 kg directly below a suspension point. Higher loads can be agreed per project.

The standard version is not walkable. For the walkable version, the combination of walkability and suspended loads is designed per project. Full load data is listed under Technical details.

Sprinklers, detection and cabling through the joint connectors

The grid is joined with connectors that have a closed opening for penetrations up to Ø 27 mm. The opening is only broken out where it is needed, so the rest of the grid stays closed.

Sprinklers, smoke detectors, cables and service ducts can be routed through the joint connectors or through the ceiling panels. Recessed luminaires and air outlets can be integrated flush with the ceiling surface, depending on the project.

Cross section of a Blix Data Ceiling profile with threaded rod and suspension unit, Blix Datagulv AS
Corner detail of Blix Data Ceiling with joint connector and grid profiles, Blix Datagulv AS

Fire class A1 and non-outgassing surfaces

With an anodised grid, Blix Data Ceiling is classified A1 according to EN 13501-1, the highest class for non-combustible materials. The ceiling is manufactured according to EN 13964.

The surfaces contain no materials that emit gases or particles, and they can be wet cleaned. This makes the ceiling suitable for clean rooms.

Ceiling for data centres, clean rooms and technical rooms

In data halls, the ceiling is used where cooling, lighting, detection and cabling must be integrated into one surface, and where installations change over time. Supply and extract air outlets and air grilles can be fitted in the ceiling. The ceiling can be combined with a raised access floor, so installations are routed both above and below the room.

The system is also suitable for clean rooms from ISO class 5 according to ISO 14644, where the ceiling can take filter fan units (FFU), and for technical rooms where installations must remain accessible.

Installation and delivery

The ceiling is delivered as a complete system and hung from a concrete slab or steel structure. The height is adjusted steplessly, from 250 mm below the slab.

Ceiling panels are removed individually from below, without dismantling the grid. The standard version is not walkable. A walkable version with walk-on plates is available on request, with a system weight of approx. 25 kg/m².

Animation showing installation of Blix Data Ceiling with aluminium grid, suspension units and lay-in panels.

Blix provides planning and engineering, design and 3D BIM modelling and installation.

Technical details

Dimensions
Standard ceiling grid1200 × 1200 mm
Custom dimensionsOn request
Maximum suspension distance1200 × 1200 mm, depending on additional loads
System height80 mm
Visible grid width55 mm
Suspension heightFrom 250 mm
System weight without ceiling panels3.15 kg/m²
System weight, walkable versionApprox. 25 kg/m² (grid, suspension, ceiling panels and walk-on plates)

Load

Load
Point load at centre of 1200 mm span200 kg at deflection L/500 (2.4 mm)
Point load directly below suspension point325 kg
Maximum area load200 kg/m², with two hangers per junction point
Maximum line load260 kg/m
Load class according to DIN EN 139643.82 kN (389.40 kg), safety factor 2.5
Breaking load, aluminium profile974.26 kg (9557.50 N)
Point loads apply withHALFEN HS 20/12, M8, 4.6 bolt
WalkabilityNot walkable as standard. Walkable version on request. Walkability combined with suspended loads is designed per project
AccessFrom below, ceiling panels are removable

Materials and finish

Materials and finish
Ceiling panelGalvanised sheet steel, L-shaped edge
Panel finishPowder-coated to RAL or other common colour systems
Gloss levelApprox. 20E (RAL 9010)
PerforationAccording to sound absorption requirements
Ceiling gridExtruded aluminium, anodised or powder-coated
Connecting partsGalvanised steel
Joint connectorsDie-cast, in X, T and L shapes
Suspension unitSuspension bolt, turnbuckle according to DIN 1480 and threaded rod, galvanised steel
Wall connection angleCoated steel, optionally powder-coated aluminium
Penetration through joint connectorUp to Ø 27 mm

Fire protection and standards

Fire protection and standards
Fire class, anodised gridA1 according to EN 13501-1
Fire class, powder-coated grid and panelsA1-s2, d0 according to EN 13501-1
Manufacturing standardsEN 13964, EN 1090 parts 2 and 3, TAIM

Environment and cleanliness

Environment and cleanliness
Outgassing and particlesNo materials that outgas or emit particles
Microbial growthLevel A, not susceptible
FormaldehydeNo significant sources
CleaningSuitable for wet cleaning, agents approved by manufacturer
Clean roomsFrom ISO class 5 according to ISO 14644
AcousticsAssessed according to ISO 11654 or ASTM C 423, depending on ceiling panel

Certification

Certificates
TAIM e.V.The ceiling system meets the requirements of the Technical Manual Metal Ceilings (TMMC) from TAIM e.V., the German association of industrial metal ceiling manufacturers.
CE markingThe system is a harmonised construction product under Regulation (EU) No 305/2011 (Construction Products Regulation).